HTTP device stopped working
Hello,
The http device stopped after few months working without any issues. Here is the debug message while trying to send the command:
Debug : 10/26/2018 19:45:41 : Devices\http : Exception : GetResponseCallbackWebException : The underlying connection was closed: An unexpected error occurred on a send. at System.Net.HttpWebRequest.EndGetResponse(IAsyncResult asyncResult)
at BOSCommon.Drivers.BOSHttpClient.GetResponseCallback(IAsyncResult result)System.IO.IOException: Authentication failed because the remote party has closed the transport stream.
at System.Net.TlsStream.EndWrite(IAsyncResult asyncResult)
at System.Net.PooledStream.EndWrite(IAsyncResult asyncResult)
at System.Net.ConnectStream.WriteHeadersCallback(IAsyncResult ar)
The encoding is UTF8 and parser type Json.
Same command gets executed when it is launched from google chome browser from the same server where the bOS is installed.
Could you please advise what the problem should be?
Thanks,
Calin
Fibaro
Hi there friends,,
I’m new to comfortclick and I’m trying to add Fibaro controller (HC2) in the software to control the Fibaro devices already in the HC2.
Can you please help and guide me on how to do that?
Your help would be highly appreciated
Error importing EIB devices from .esf
Hi,
When I import the .esf file in bOS Configurator I get the error "Error importing EIB devices from .esf" I use ETS5, I tried with very simple knx program.
Modbus limit
Hello. I am facing strange behaviour of Modbus device. I am sending about 150 values thru Modbs and after test I got an error Device is not connected. I see it been connected and immediately disconnected. So I try it with fewer values and it works. After many tries I got on point where it works but when I add one more Duble value it stop working. So I start wondering is there any limit for Modbus point like how many you can add under one Modbus device? I ended up utilising two Modbus devices so it works. Same issue on Jigsaw and Windows Server.
Response timeout with Vallox modbus
Hey,
We have 2 similar buildings, with same settings and hardware. We use Vallox ventilation and control them with USB modbus dongle. But after tomorrow we started to get response timeouts on one building(other building has no timeouts). The whole modbus line feels slower too(chaning the vent speeds works but it feels slower than before). I know the log used to be clean without any timeouts. Now im trying to debug what is causing it. So far it feels like they are responding but not for all requests. Here is a small screenshot where i get timeouts for ventilation State(4609) and Fan speed(4353)
Is there any other way to know witch ventilation is not responding(we have total of 19 units) The path only show the modbus dongle. I have looked at the times too and compared them to the log monitor, but it seams to me that the response timeouts are random. Sometimes they get awnsers sometimes they don't. Here are my settings for the USB dongle:
Other building works just fine with the same settings, and changing vent speeds feels faster to me.
Confirmation windows
Dear,
if I select Enable form in the control type MouseDownButton, when I push the button in the client (I tested in IOS app) the confirmation windows doesn’t appear
Regards
exporting mbus values
Hey,
Is it possible to export mbus values to excel or pdf automatically? What i would like to do is: make a program that exports current mbus-modbus tcp values on the first day of the month every month to a excel table.
Has anyone done this?
Image appers black
Hello everyone
I have a problem in site. In the application BOSCliente i have a connection with the video camera and at the beginning everything was working correctly. The client had to change the router but now the image appears all black. I can access the camera externally and everything works fine but the application does not work. can someone help me?
Thank you
Luis Faustino