MODBUS WITH PRODUAL HLS 44 Thermostat
I am trying to integrate Modbus Thermostat ( Produal HLS 44 ) with Jigsaw Z wave via RS 485 ( RTU ). The register details are mentioned below :-
Holding Register Address 1 ( 40001 ) = FAN SPEED CONTROL WRITE
Holding Register Address 2 ( 40002 ) = SET POINT WRITE
Input Register Address 18 ( 30018 ) = SET POINT BY USER
Input Register Address 19 ( 30019 ) = FAN CONTROL BY USER
Those Address were verified using MODSCAN 32 and found to be correct.
Now in jigsaw, the scenario is different. The setup was :-
ACTUALLY ADDRESS 18 IS FOR SET POINT BUT I AM GETTING THE SET POINT IN ADDRESS 17 ( 18 - 1 )
SIMILARLY ADDRESS 19 IS FOR FAN SPEED AND I AM GETTING IN ADDRESS 18 ( 19 - 1)
So what we have seen is for input register, we need to deduct -1 with the address mentioned in datasheet.
REGARDING THE HOLDING REGISTER 1 AND 2, IT IS NOT WORKING. I AM ABLE TO GET DATA FROM INPUT REGISTER BY DEDUCTING THE ADDRESS BY 1. BUT I AM NOT ABLE TO WRITE ANYTHING IN HOLDING REGISTER.
ALSO THE VALUE FROM INPUT REGISTER IS LIKE 280, 275, 220. WE NEED THE VALUE LIKE 28, 27.5, 22 ( divided by 10 ).
CAN YOU PLEASE SUPPORT ?
KNX ETS file
I've received a ETS file but the extension is *.knxproj
How can I convert this in a esf file?
Thank you
Andrea
HEX tof TEXT
Jestem nowy i mam problem z wyświetlaniem aktualnego tekstu ze wzmacniacza DENON AVR. Tekst jest wyświetlany tylko w formacie HEX, czy wiesz, ile wartości można przekształcić w tekst?A.
Variable Cylic Sending of Commands
To reduce traffic, I generally set commands to send cyclically at around 5 minute intervals.
In certain circumstances, I would want to "boost" that to get 30 second responses temporarily to closely monitor conditions.
Is there a way to Send Cyclically on a variable time period?
Hunter Douglas PowerView blinds on bOS?
I'd like to control some Hunter Douglas PowerView blinds and I'm curious if anyone has figured out how to do that. I'd appreciate your ideas.
Michael
Displaying IP Camera on an Amazon Echo Show?
I've successfully connected to an IP Camera using bOS. Now, I'd like to be able to show it on an Amazon Echo Show, but it doesn't look like Alexa Skills support showing IP Cameras.
Has anyone had any luck doing this?
Thanks,
Michael
Import 3 byte KNX value
I´m trying to import a 3 byte status value that needs to be put through the bit converter. Altough the only option I find is to import it as a date or time value. How do I add it as a generic 3byte value?
z-wave node description shows script error message
Hi
Clicking on the z-wave "Node Settings" button for a device in Devices\Z-Wave brings up the script error message shown below.
This happens for all z-wave devices. I'm running bOS on a Jigsaw device, configurator on Windows 7 and all are fully up to date with latest ComfortClick releases. I can access and browse the internet from my PC. Can you help please?
I am not sure how to configure http > Boolean with url /api
I am not sure how to configure http > Boolean with below url /api
I have to pass l1498904289859 to open window http://192.168.2.109:8080/send?deviceMac=b4430dd11511&codeId=l1498904289859 Close window l1498900850560 http://192.168.2.109:8080/send?deviceMac=b4430dd11511&codeId=l1498900850560
using browser to enter url its working and programme > set the http request also work
Customer support service by UserEcho