DSC IT-100 PC-Link
Hello good afternoon!
I am setting up the DSC control panel, PowerSeries PC1832 with IT-100 module, but when I'm with the PC-Link cable connected in the central PC1832 can communicate with ComfortClick the IT-100, when I remove the central caboPC-Link and continue with serial cable connected the IT-100 and the server can not communicate with the comfortclick.
What could be happening?
Thank you.
Customer support service by UserEcho
Hello,
try to Reset Module Supervision in Installer mode (code 902) wait few seconds and re-check the Modules (code 903).
Regards