+1

Satel Integra and Ethm-1 connection issue

Wijdan Maani Takrouri 3 years ago updated by Miroslav Hajduk 3 years ago 2

Hello,

Problem:
can read partitions and zones from Integra through Integration via Ethm1, But we can't arm nor disarm partitions.

HW. Info: 

  • Integra 64 firmware version 1.18
  • Ethm1 Plus firmware version 2.07

SW. Info:

  • The user account that has been used to Authorize connection has the privilege to arm and disarm.
  • the same user can make arm and disarm from a physical keypad.
  • we had ensured that the user code is inserted correctly in the integration for a proper connection.
  • The commends that are sent from the integration device built as “2015-03-19 Version of Specification communication protocol
  • User Code is: 1478
    Arm Command Form: 254 254 128 20 120 255 255 255 255 255 255 1 0 0 0 162 73 254 13
    Disarm Command Form: 254 254 132 20 120 255 255 255 255 255 255 1 0 0 0 229 18 254 13

there is something worth to mention here we had a problem to connect Dloadx -> Ethm1 TCP/IP, although the connection from Ethm1 -> Dloadx has made successfully.


I couldn't figure out what is the exact problem, I am looking forward to your suggestions and solution

Thanks For your time

Hello,

in bOS Configurator, select log button (bottom left) select Debug tab and click Record. Then try to arm/disarm the panel and see what info log provides.

Best regards.

Isn't that issue because SATEL allows only one concurrent connection to ETHM modules? 

I have experienced connection issues till I have find out that in SATEL ETHM manual. So, your old sessions could block you. 

I didn't find out when old session ends, but it could create many issues. 

SATEL confirmed that more concurrent connections more ETHM modules are necessary. 

Such a fail from them. I don't understand this limitation and it was not explained.